HL 353.02 Heat Distribution And Control In Heating Systems Didactic Equipment Vocational Education Equipment Thermal Lab Equipment
Two independent heating circuits with control devices: heating circuit with one subcircuit and with two subcircuits
Features
- setup of a complete domestic heating system together with hot water generator HL 353
- two independent heating circuits:
-- heating circuit with one subcircuit
-- heating circuit with two subcircuits
- control devices for both heating circuits
Learning objectives/experiments
- design of a room heating system with controller and actuator
-- temperature-led heating controller (outside temperature) with three-way mixing valve
-- simulator for varying outside temperature
- function and design of a room heating system divided into sections
- hydronic balancing of heating circuits with multiple radiators
- function and design of commercially available heating technology components
- measurement of differential pressures, temperatures and flow rates
- energy calculation and evaluation of emitted heating capacity based on measured quantity of heat
- reading and comprehension of symbols and process schematics
Specification
[1] together with hot water generator: setup of a complete domestic heating system with 2 independent heating circuits
[2] heating circuit with one subcircuit contains 2 flat radiators, circulating pump, heating controller with 3-way mixing valve and simulator for variation of outside temperature

[3] heating circuit with two subcircuits contains 4 radiators, circulating pump, 2 heating controllers, 2 solenoid valves
[4] flow control valves for hydronic balancing in heating circuit with two subcircuits
[5] measurement of flow rate and pressure
[6] 9 measuring points for differential pressure and temperature (temperature measurement via sensors of HL 353)
[7] hot water connections with quick-release couplings
Technical data
1 Flat radiator, aluminium
- heating capacity: 545W at feed flow 70°C, return flow 55°C and ambient temperature 20°C
1 Flat radiator, steel
- heating capacity: 665W at feed flow 70°C, return flow 55°C and ambient temperature 20°C
4 Radiators, steel
- heating capacity: 492W at feed flow 70°C, return flow 55°C and ambient temperature 20°C
2 Circulating pumps
- max. power consumption: 25/35/45W
- max. flow rate: 3000L/h
- max. head: 3,8m
3 Heat meters: 20...90°C, 1,5m3/h
Measuring ranges
- pressure: 2x 0...1,6bar
- differential pressure: 0...0,25bar
- flow rate: 3x 40...400L/h
230V, 50Hz, 1 phase
LxWxH:2500x760x2000mm
Weight: approx. 240kg